Zelos Modbus

A Zelos extension for the Modbus protocol. Read, write, and monitor registers from PLCs, power meters, sensors, and other Modbus devices over TCP or RS232/RS485 serial.

Features

  • πŸ“‘ Modbus TCP & RTU: Connect over Ethernet or RS232/RS485 serial
  • πŸ“Š All register types: Holding, input, coils, and discrete inputs
  • πŸ“„ Register map files: Define your device layout in a simple JSON file
  • β˜€οΈ SunSpec discovery: Inverters, meters and batteries map themselves at connect (SUNSPEC.md)
  • πŸ” Auto-scan: A device without a map finds its registers at start and streams them
  • ✏️ Read & write actions: Interactive register access from the Zelos App

Quick Start

Install the Modbus extension, add a device by its address, start it and plot an auto-scanned register

From the CLI, on the agent that can reach the device:

zelos extensions install zeloscloud/zelos-extension-modbus
zelos extensions start zeloscloud.zelos-extension-modbus \
  --config '{"connections": [{"transport": "tcp", "host": "192.168.1.100", "port": 502, "devices": [{"unit_id": 1}]}]}'

A device without a register map is auto-scanned.

In the app:

  1. Install the extension from the Zelos App
  2. Configure a connection (TCP or RTU) and its devices (unit ID; a register map file, SunSpec, or nothing: auto-scan)
  3. Start the extension to begin streaming data
  4. View real-time register values in your Zelos App

Configuration

Connections

A connection is a TCP endpoint or a serial port. Its devices share the link and are polled one request at a time.

Setting Default Description
Transport tcp tcp or rtu
Name endpoint Trace name; defaults to the sanitized host or serial port (10_0_0_5, dev_ttyUSB0)
Host / Port 127.0.0.1 / 502 TCP only
Serial Port RTU only (/dev/ttyUSB0, COM3)
Baudrate / Parity / Stop Bits / Data Bits 9600 / N / 1 / 8 RTU only; must match the devices
Devices One or more, below

Devices

Setting Default Description
Unit ID 1 Modbus unit ID; unique per connection
Name unit<ID> Trace name; unique per connection
Register Map file file or sunspec (see SUNSPEC.md)
Register Map File JSON register map, path or inline; empty = auto-scan
Auto-scan on Without a map file, discover and poll the device's registers; off = nothing polled
Rate TCP 1 s / RTU 10 s Poll rate (s) for registers without their own rate; 0 = not polled

Names are letters, digits, space, _ or -.

Advanced

Applies to every connection and device; a register map device block overrides it per key.

Setting Default Description
prefix Modbus Trace source: Modbus/10_0_0_5/unit1/voltage; cleared = one source per connection
default_rate TCP 1.0, RTU 10.0 Poll rate (s) when neither register nor device sets one
log_level INFO DEBUG, INFO, WARNING, ERROR
timeout 3.0 Seconds to wait for each response
retries 1 Extra attempts per request
request_delay_ms 0 Minimum gap between requests (RS485 gateways, slow RTU devices)
connect_delay_ms 0 Pause after each (re)connect
retry_unreachable_at_start off A connection unreachable at start is retried instead of stopping the extension
demote_after 3 Consecutive timeouts before a device is demoted
demote_max_s 300 Longest wait between probes of a demoted device
block_reads on Coalesce contiguous registers into range reads
max_block_size 125 Max registers per range read
max_bit_block_size 2000 Max coils / discrete inputs per range read
max_read_gap 0 Max unmapped registers bridged within a block
write_mode auto auto (FC 6 single / FC 16 multi) or fc16
allow_raw_writes off Enable the raw write actions; read-only map addresses stay refused

Serial/USB troubleshooting: DEBUG.md.

Polling

Rate precedence: register rate > device Rate > default_rate; a map min_rate floors it.

Condition Behavior
Rate not met get_status reports requested vs achieved rate; over 100% for 30 s warns once
Device not answering Demoted after demote_after timeouts: skipped, probed from 10 s doubling to demote_max_s
Link down Reconnect from 3 s doubling to 60 s
Unreachable at start Extension stops with an ERROR naming the connection; with retry_unreachable_at_start, retried as a link down while the others poll
Exception 02/03 Block skipped, retried every 10 min; verify finds the bad registers

Auto-scan

A device without a register map file discovers its registers at start (reads only) and polls each as it is found, as a raw register. It reruns on every start; save_map writes the finds as a map file. Each register is its own trace event (~0.75 MB each), so save and trim the map for large devices.

Raw registers

Unmapped registers trace one event per register: holding register 123 is holding_registers/123, field hr_123 (likewise input_registers/ ir_, coils/ coil_, discrete_inputs/ di_), as raw uint16 or bool.

Register Map

A register map file defines which registers to read and how to decode them. Event names become Zelos trace events, and register names become fields within those events.

{
  "name": "power_meter",
  "events": {
    "voltage": [
      {"name": "L1", "address": 1, "datatype": "float32", "unit": "V"},
      {"name": "L2", "address": 3, "datatype": "float32", "unit": "V"}
    ],
    "setpoints": [
      {"name": "limit", "address": 101, "datatype": "uint16", "writable": true}
    ],
    "status": [
      {"name": "firmware", "address": 1, "type": "input"},
      {"name": "door_open", "address": 1, "type": "discrete_input"}
    ]
  }
}

register_map_file is a path on the agent's host, or the map JSON inline (starting with {).

Addressing

Addresses are 1-based, as in vendor sheets: holding register 40001 is sent as wire address 40000. A map numbered from wire 0 sets "device": {"address_base": 0}.

Register Fields

Field Required Default Description
address Yes Register address
name No r<address> Field name, unique per event
type No holding holding, input, coil, discrete_input
datatype No uint16 See Data Types
unit No Display unit
scale No 1.0 Scale factor; a scaled integer decodes to a float
rate No device rate Poll rate (s); 0 = not polled
byte_order No big See Byte Order
writable No false Allow writes (holding registers and coils)
length strings Registers a string spans
scale_ref No Integer register in the same event holding a power-of-10 exponent
invalid No Raw values meaning "not implemented", logged as null
values No Enum labels, {"0": "off", "1": "on"}

An optional top-level device block carries device quirks, e.g. "device": {"max_block_size": 60, "byte_order": "big_swap"}:

Key Description
max_block_size, max_bit_block_size, max_read_gap, write_mode Override Advanced
byte_order Default for registers without one
min_rate Floor (s) on every register's rate
close_after_sweep Close the connection between sweeps (single-connection devices)
address_base 1 (default) or 0

Data Types

Type Registers Type Registers
bool 1 uint32 2
uint16 1 int32 2
int16 1 float32 2
uint64 4 int64 4
float64 4 string length

Strings are ASCII, 2 bytes per register, read-only.

Byte Order

Wire order of a 32-bit value, A = most significant byte.

Order Wire bytes Common in
big AB CD Most devices
little DC BA
big_swap CD AB Modicon/Schneider PLCs
little_swap BA DC

Scan

Point scan at an unknown device to find its unit IDs, identity, valid address ranges, and a draft register map. Scan only reads (FC 01-04, 43/14, 17). Some devices clear latched alarms or counters on read; review before scanning production equipment.

uv run main.py scan 192.168.1.100 --out draft.json         # JSON report on stdout
uv run main.py scan /dev/ttyUSB0 -t rtu --autodetect --units 1-10
uv run main.py verify 192.168.1.100 registers.json --unit 3  # exits 1 on any problem

The draft lists every readable address as a raw uint16 / bool, read-only; set datatypes, byte order and scaling from the datasheet.

With the extension stopped, the same runs as actions:

Action Description
auto_config The config form's Auto-configure: finds units on each connection and adds them, SunSpec where detected
scan_device Full scan of a host or serial port; slow
verify_map Check a map file against the device register by register
list_serial_ports Serial ports on the agent's machine

Actions

Actions are available from the Zelos App and to app extensions as Modbus/<action>. Every action but list_devices takes a device selector, <connection>/<device> (e.g. 10_0_0_5/unit1).

Action Description
list_devices Every device with its endpoint, trace path, map, and health
get_status Connection health, read counters, requested vs achieved rate
get_snapshot Last polled value per event/name, no device I/O
read_register Read raw registers or bits by address, type, and count
write_single_register Write one holding register (FC 6)
write_registers Write 1-123 holding registers (FC 16)
write_coil Write ON/OFF to a coil (FC 5)
read_named_register Read a mapped register by event/name
write_named_register Write a mapped register by event/name, in engineering units
list_registers Register catalog: path, address, datatype, scale, unit, rate
list_writable_registers Same catalog, writable registers only
save_map Write the device's current map (loaded or auto-scanned) to a JSON file

Raw writes need allow_raw_writes and never touch an address the map marks read-only. Every write returns outcome: ok, refused (not written), or unknown (no response: the write may have landed, read back before retrying).

Development

just install   # Install dependencies
just check     # Run linting
just format    # Auto-format code
just test      # Run tests
just sim       # Power-meter simulator to point a connection at (127.0.0.1:5020)
uv run main.py demo-server -u 1 -u 2   # Separate meters on unit IDs 1 and 2
uv run main.py demo-server --scan-target -p 5030   # Sparse device for scan (--zero-fill, --sunspec, --serial)
uv run python -m zelos_extension_modbus.demo.sunspec_sim --port 5021   # Full SunSpec inverter (register_map sunspec)

demo-server --sunspec only answers the SunSpec marker (enough for scan and Auto-configure); sunspec_sim serves full models for SunSpec discovery and polling.

For a live local test, run just sim and configure a connection at 127.0.0.1:5020 with a device using register map zelos_extension_modbus/demo/power_meter.json (config.json is gitignored; set it via the Zelos App config dialog or by hand).

Links

CLI Usage

For advanced command-line usage (tracing without the Zelos App), see cli/README.md.